Commit af7d9112 authored by Ivan Tyagov's avatar Ivan Tyagov

Firts modbus server for lime2.

parent 5299d8de
......@@ -34,65 +34,11 @@ log.setLevel(logging.DEBUG)
def run_async_server():
# ----------------------------------------------------------------------- #
# initialize your data store
# ----------------------------------------------------------------------- #
# The datastores only respond to the addresses that they are initialized to
# Therefore, if you initialize a DataBlock to addresses from 0x00 to 0xFF,
# a request to 0x100 will respond with an invalid address exception.
# This is because many devices exhibit this kind of behavior (but not all)
#
# block = ModbusSequentialDataBlock(0x00, [0]*0xff)
#
# Continuing, you can choose to use a sequential or a sparse DataBlock in
# your data context. The difference is that the sequential has no gaps in
# the data while the sparse can. Once again, there are devices that exhibit
# both forms of behavior::
#
# block = ModbusSparseDataBlock({0x00: 0, 0x05: 1})
# block = ModbusSequentialDataBlock(0x00, [0]*5)
#
# Alternately, you can use the factory methods to initialize the DataBlocks
# or simply do not pass them to have them initialized to 0x00 on the full
# address range::
#
# store = ModbusSlaveContext(di = ModbusSequentialDataBlock.create())
# store = ModbusSlaveContext()
#
# Finally, you are allowed to use the same DataBlock reference for every
# table or you you may use a seperate DataBlock for each table.
# This depends if you would like functions to be able to access and modify
# the same data or not::
#
# block = ModbusSequentialDataBlock(0x00, [0]*0xff)
# store = ModbusSlaveContext(di=block, co=block, hr=block, ir=block)
#
# The server then makes use of a server context that allows the server to
# respond with different slave contexts for different unit ids. By default
# it will return the same context for every unit id supplied (broadcast
# mode).
# However, this can be overloaded by setting the single flag to False
# and then supplying a dictionary of unit id to context mapping::
#
# slaves = {
# 0x01: ModbusSlaveContext(...),
# 0x02: ModbusSlaveContext(...),
# 0x03: ModbusSlaveContext(...),
# }
# context = ModbusServerContext(slaves=slaves, single=False)
#
# The slave context can also be initialized in zero_mode which means that a
# request to address(0-7) will map to the address (0-7). The default is
# False which is based on section 4.4 of the specification, so address(0-7)
# will map to (1-8)::
#
# store = ModbusSlaveContext(..., zero_mode=True)
# ----------------------------------------------------------------------- #
store = ModbusSlaveContext(
di=ModbusSequentialDataBlock(0, [17]*100),
co=ModbusSequentialDataBlock(0, [17]*100),
hr=ModbusSequentialDataBlock(0, [17]*100),
ir=ModbusSequentialDataBlock(0, [17]*100))
di=ModbusSequentialDataBlock(0, [0]*10),
co=ModbusSequentialDataBlock(0, [0]*10),
hr=ModbusSequentialDataBlock(0, [0]*10),
ir=ModbusSequentialDataBlock(0, [0]*10))
store.register(CustomModbusRequest.function_code, 'cm',
ModbusSequentialDataBlock(0, [17] * 100))
context = ModbusServerContext(slaves=store, single=True)
......@@ -103,49 +49,17 @@ def run_async_server():
# If you don't set this or any fields, they are defaulted to empty strings.
# ----------------------------------------------------------------------- #
identity = ModbusDeviceIdentification()
identity.VendorName = 'Pymodbus'
identity.ProductCode = 'PM'
identity.VendorName = 'Nexedi'
identity.ProductCode = 'Lime2.PLC'
identity.VendorUrl = 'http://github.com/bashwork/pymodbus/'
identity.ProductName = 'Pymodbus Server'
identity.ModelName = 'Pymodbus Server'
identity.MajorMinorRevision = '2.3.0'
identity.MajorMinorRevision = '0.0.1'
# ----------------------------------------------------------------------- #
# run the server you want
# ----------------------------------------------------------------------- #
# TCP Server
StartTcpServer(context, identity=identity, address=("localhost", 502),
custom_functions=[CustomModbusRequest])
# TCP Server with deferred reactor run
# from twisted.internet import reactor
# StartTcpServer(context, identity=identity, address=("localhost", 5020),
# defer_reactor_run=True)
# reactor.run()
# Server with RTU framer
# StartTcpServer(context, identity=identity, address=("localhost", 5020),
# framer=ModbusRtuFramer)
# UDP Server
# StartUdpServer(context, identity=identity, address=("127.0.0.1", 5020))
# RTU Server
# StartSerialServer(context, identity=identity,
# port='/dev/ttyp0', framer=ModbusRtuFramer)
# ASCII Server
# StartSerialServer(context, identity=identity,
# port='/dev/ttyp0', framer=ModbusAsciiFramer)
# Binary Server
# StartSerialServer(context, identity=identity,
# port='/dev/ttyp0', framer=ModbusBinaryFramer)
if __name__ == "__main__":
run_async_server()